MCB

 Minture Circuit Breakers   Ego

  • Protection against both overload and short circuit
  • High breaking capacity
  • Contact position indication
  • According to IEC 60898

 Minture Circuit Breakers   Ego 400

 No. of poles: 1,1+N,2, 3

Rated current In: (6,10,13,16,20,25,32,40,50,63)A

Tripping characteristics: B.C & K

Rated breaking capacity( Icu): 6000 A

Rated voltage Un: 230/ 400 V~

Connection terminal: Pillar terminal with clamp

Connection capacity: Rigid conductor up to 25mm2

Minture Circuit Breakers   Ego 600

No. of poles: 1, 1+N,2, 3

Rated current In: (6,10,13,16,20,25,32,40,50,63)A

Tripping characteristics: B.C & K

Rated breaking capacity( Icu): 6000 A

Rated voltage Un: 230/ 400 V~

Connection terminal: Screw terminal and Pillar terminal with clamp

Connection capacity: Rigid conductor up to 25mm2

Minture Circuit Breakers   Ego 1000

No. of poles: 1, 1+N,2, 3

Rated current In: (6,10,13,16,20,25,32,40,50,63)A

Tripping characteristics: B.C & K

Rated breaking capacity( Icu): 10000 A

Rated voltage Un: 230/ 400 V~

Connection terminal: Screw terminal and Pillar terminal with clamp

Connection capacity: Rigid conductor up to 25mm2

 

Tripping diagram

 

Tripping Characteristics K

 

 

 

Tripping Characteristics C

Tripping Characteristics B

 

 

RESIDUAL CURRENT CIRCUIT BREAKERS      Ego-RC

  • Provides Protection against earth fault/leakage current and function of isolation
  • High breaking current withstand capacity
  • Applicable to terminal and Pin/fork type busbar connection
  • Fire resistant  plastic parts endures abnormal heating and strong impact
  • Automatically disconnect the circuit when earth fault/leakage current occurs and exceeds the rated sensitivity
  • Independent of power supply and line voltage , and free from external interference, voltage fluctuation

                                     

No. of poles: 2, 4

Rated current In:  ( 25,40,63)A

Rated Voltage:  240/415V AC

Rated residual Operating current I∆n (mA): 10,30,100,300,500

Rated conditional breaking current Inc: 6000 A

Rated conditional residual breaking current I∆c: 6000 A

Connection terminal: Screw terminal and Pillar terminal with clamp

Connection capacity: Rigid conductor up to 25mm2

 

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION    Ego-RCO

No of Poles: 1P+N , 3P+N

Rated Current: UP to 63 A

Rated Voltage: 230/ 400 V~

Rated breaking capacity( Icu): 10000 A

Connection terminal: Screw terminal and Pillar terminal with clamp

Connection capacity: Rigid conductor up to 25mm

Electro- mechanical endurance: 4000

Connection capacity: Rigid conductor up to 25mm2

Minture Circuit Breakers   Ego-DC

  • Applicable for  Solar Photovoltaic System Protection and Traction
  • Protection against both overload and short circuit
  • High breaking capacity
  • Contact position indication
  • Applicable to terminal and Pin/fork type busbar connection

Frame degree rated current (A):63

Rated current In (A): (6,10,13,16,20,25,32,40,50,63)A

Ue Rated Operating voltage (V DC): 1P250, 2P500,3P750,4P1000

Rated insulation voltage Ui (V DC): 1P:500V  2P:500V  3P:750V  4P:1000V

Ultimate breaking capacity Icn (KA): 10

Run breaking capacity Ics (%Icu): 75%

Curve type: B(4-7In),C(7-15In)

Trip type :Thermal-magnetic

Relative humidity: 95%

Inquiry

QR Code Product